MAIN SPECIFICATIONS
Breaking Capacity 10 kA Icu at 660…690 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity Code N 50 kA 415 V AC
Contacts Type And Composition 63 A at 40 °C
Control Type toggle
Product Or Component Type circuit breaker
Range Of Product ComPacT NSXm new generation
Trip Unit Name TM-D
[Ie] Rated Operational Current toggle
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Device Short Name NSXm 100N
EAN13 3606481991614
Mounting Support backplate
Network Type AC
Neutral Position left
Protected Poles Description 3D
Range ComPacT new generation
Range Name ComPacT NSXm (2021)
Suitability For Isolation yes conforming to IEC 60947-2
Trip Unit Protection Functions LI
Trip Unit Technology thermal-magnetic
Utilisation Category category A
COMPLEMENTARY
Communication Network Type 690 V AC 50/60 Hz
Current Transformer Type N 50 kA 415 V AC
Interlocked Device 10 kA Icu at 660…690 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
Product Name ComPacT NSXm new generation
[Ics] Rated Service Breaking Capacity 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
[In] Rated Current 63 A at 40 °C
9 Mm Pitches 12 module
Colour grey (RAL 7016)
Connection Pitch 27 mm without spreaders
35 mm with spreaders
Connections – Terminals compression lug/busbar
Depth 80 mm
Device Application distribution
protection
Downside Connection front
Electrical Durability 10000 cycles at 440 V In
10000 cycles at 690 V In/2
20000 cycles at 440 V In/2
5000 cycles at 690 V In
Height 137 mm
Local Signalling flag (green) for presence of auxiliary contacts
Long Time Delay Adjustment Type fixed
Long Time Pick-up Adjustment Range 0.7…1 x In
Long Time Pick-up Adjustment Type Ir adjustable
Magnetic Tripping Current 800-800 A
Mechanical Durability 20000 cycles
Mounting Mode fixed
Net Weight 1.42 kg
Network Frequency 50/60 Hz
Number Of Slots 1 slot(s) for alarm switch SD
1 slot(s) for auxiliary switch OF
1 slot(s) for voltage release MN or MX
Power Losses 5.58 W
Quantity Per Set set of 1
Short-time Delay Adjustment Type fixed
Short-time Pick-up Adjustment Type Isd fixed
Trip Unit Rating 63-63 A at 40 °C
Upside Connection front
Width 108 mm
[Uimp] Rated Impulse Withstand Voltage 8 kV
[Ui] Rated Insulation Voltage 800 V