| Output | |
| Max Configurable Power (Watts) | 4.0kWatts / 5.0kVA |
| Output Voltage Distortion | Less than 5 % |
| Output Voltage Note | Configurable for 220 : 230 or 240 nominal output voltage |
| Efficiency at Full Load | 96.0% |
| Output Frequency (sync to mains) | 47 – 53 Hz For 50 Hz nominal Sync to mains |
| Other Output Voltages | 220, 240 |
| Load Crest Factor | 3 : 1 |
| Topology | Line interactive |
| Waveform type | Sine wave |
| Transfer Time | 2 ms typical : 4 ms maximum |
| Input | |
| Input frequency | 50/60 Hz +/- 3 Hz Auto-sensing |
| Input voltage range for main operations | 151 – 302 Adjustable, 160 – 286V |
| Batteries & Runtime | |
| Battery type | VRLA |
| Typical recharge time | 3hour(s) |
| Replacement Battery | RBC55 |
| Expected Battery Life (years) | 3 – 5 |
| RBC Quantity | 2 |
| Battery Charge Power (Watts) | 542 Watts |
| Communications & Management | |
| Interface Port(s) | DB-9 RS-232, SmartSlot |
| Control panel | LED status display with on line : on battery : replace battery and overload indicators |
| Audible Alarm | Audible and visible alarms : configurable delays |
| Surge Protection and Filtering | |
| Surge energy rating | 480Joules |
| Filtering | Full time multi-pole noise filtering : 5% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Physical | |
| Maximum Height | 222MM, 22.2CM |
| Maximum Width | 483MM, 48.3CM |
| Maximum Depth | 660MM, 66.0CM |
| Net Weight | 97.73KG |
| Conformance | |
| Approvals | C-Tick, CE, EN 50091-1, EN 50091-2, GOST, GS Mark, VDE |
| Standard warranty | 2 years repair or replace |