| Output | |
| Max Configurable Power (Watts) | 16.0kWatts / 20.0kVA |
| Output Voltage Note | Configurable for 400 or 415 V 3 Phase nominal output voltage |
| Output Voltage Distortion | Less than 5 % |
| Output Frequency (sync to mains) | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz Sync to mains |
| Other Output Voltages | 220, 240 |
| Load Crest Factor | 3 : 1 |
| Topology | Double conversion online |
| Waveform type | Sine wave |
| Overload Operation | 60 seconds at 125% and 30 seconds at 150% |
| Bypass | Built-in static bypass, Internal bypass (automatic and manual), Optional external bypass |
| Input | |
| Input frequency | 40 – 70 Hz Auto-sensing |
| Input voltage range for main operations | 160 – 280V |
| Input Total Harmonic Distortion | Less than 5 % for full load |
| Other Input Voltages | 220, 240 |
| Input Power Factor at Full Load | 0.98 |
| Batteries & Runtime | |
| Battery type | Lead-acid battery |
| Included Battery Modules | 4 |
| Typical recharge time | 2.5hour(s) |
| Nominal Battery Voltage | +/- 192 V (split battery referenced to neutral) |
| Replacement Battery | APCRBC140 |
| Expected Battery Life (years) | 3 – 5 |
| RBC Quantity | 4 |
| Battery Charge Power (Watts) | 1.53kWatts |
| Efficiency in Battery Operation | 93.0 % |
| Communications & Management | |
| Interface Port(s) | DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot |
| Control panel | Multifunction LCD status and control console |
| Audible Alarm | Audible and visible alarms : configurable delays |
| Emergency Power Off (EPO) | Yes |
| Pre-Installed SmartSlot™ Cards | AP9631 |
| Surge Protection and Filtering | |
| Filtering | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Physical | |
| Maximum Height | 533MM, 53.3CM |
| Maximum Width | 432MM, 43.2CM |
| Maximum Depth | 773MM, 77.3CM |
| Net Weight | 247.73KG |
| Conformance | |
| Approvals | BSMI, EN/IEC 62040-1-1, EN/IEC 62040-2, VDE |
| Standard warranty | 2 years repair or replace |