Output | |
Max Configurable Power (Watts) | 280 Watts / 450VA |
Output Voltage Distortion | Less than 5 % at full load |
Output Frequency (sync to mains) | 47 – 53 Hz For 50 Hz nominal Sync to mains, 57 – 63 Hz For 60 Hz nominal Sync to mains |
Topology | Line interactive |
Waveform type | Stepped approximation to a sinewave |
Transfer Time | 4 ms typical : 8 ms maximum |
Input | |
Input frequency | 50/60 Hz +/- 3 Hz Auto-sensing |
Input voltage range for main operations | 151 – 302 Adjustable, 195 – 265V |
Batteries & Runtime | |
Battery type | Lead-acid battery |
Typical recharge time | 5hour(s) |
Replacement Battery | RBC18 |
Expected Battery Life (years) | 3 – 5 |
RBC Quantity | 1 |
Battery Charge Power (Watts) | 22 Watts |
Communications & Management | |
Interface Port(s) | DB-9 RS-232 |
Control panel | LED status display with on line : on battery : replace battery and overload indicators |
Audible Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
Emergency Power Off (EPO) | Optional |
Surge Protection and Filtering | |
Surge energy rating | 320Joules |
Data Line Protection | RJ11 2-Way Modem/Fax/DSL splitter with protection (four wire dual lines), RJ45 10/100 Base-T Ethernet protection |
Filtering | Full time multi-pole noise filtering : 0.7% IEEE surge let-through : zero clamping response time : meets UL 1449 |
Physical | |
Maximum Height | 44MM, 4.4CM |
Maximum Width | 432MM, 43.2CM |
Maximum Depth | 383MM, 38.3CM |
Net Weight | 10.18KG |
Conformance | |
Approvals | C-Tick, CE, EAC, GOST, TISI, VDE |
Standard warranty | 2 years repair or replace |
Sustainable Offer Status | |
RoHS | Compliant |
PEP | Available in Documentation tab |
EOLI | Available in Documentation tab |