Schneider Miniature circuit breaker (MCB), Acti9 C120H, 4P, 125A, C curve, 15000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2)

Rp4.672.290

Deskripsi
Main
Range of product C120
Range Acti9
Product name C120
Product or component type Miniature circuit-breaker
device short name C120H
Device application Distribution
Poles description 4P
Number of protected poles 4
[In] rated current 125 A at 30 °C
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 15000 A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 380…415 V AC 50/60 Hz
<= 500 V DC
220…240 V AC 50/60 Hz
440 V AC 50/60 Hz
230…400 V AC 50/60 Hz
magnetic tripping limit 5…10 x In
[Ics] rated service breaking capacity 7500 A 50 % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
5 kA 50 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – <= 500 V DC
Limitation class 3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support 35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility NO
9 mm pitches 12
Height 81 mm
Width 108 mm
Depth 73 mm
Product weight 0.82 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 5000 cycles conforming to IEC 60947-2
Locking options description Handle sealable with cable diameter 0.7mm in OFF or ON position
Connections – terminals Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible
Wire stripping length 15 mm
Tightening torque 3.5 N.m
Earth-leakage protection Separate block
Acti9 C120_A9N18481-dataseet