Huawei TP48200A-D14A1 Telecom Power Cabinet
Rp6.660.000
Category |
Item |
Specifications |
---|---|---|
Environmental conditions |
Operating temperature |
–10ºC to +50ºC (+14ºF to +122ºF) |
Storage temperature |
–40°C to +70°C (–40°F to +158°F) |
|
Transportation temperature |
–40°C to +70°C (–40°F to +158°F) |
|
Operating humidity |
5%–95% RH (non-condensing) |
|
Storage humidity |
5%–95% RH (non-condensing) |
|
Altitude |
0–4000 m (013123.2 ft) When the altitude ranges from 3000 m (9842.4 ft) to 4000 m (13123.2 ft), the operating temperature is derated by 1ºC (1.8ºF) for each additional 100 m (328.08 ft). |
|
AC input |
Input mode |
Single phase three wire (L, N, and PE) |
Input voltage |
90–290 V AC (rated voltage: 220 V AC) |
|
Input frequency |
40–65 Hz (rated frequency: 50/60 Hz) |
|
Power factor |
≥ 0.99 (rated load) |
|
DC output |
Output voltage range |
–42 V DC to –58V DC |
Default output voltage |
–53.5 V DC |
|
Maximum output power |
Number of rectifiers multiplied by the output power of a single rectifier |
|
Regulated voltage precision |
≤ 1% |
|
Peak-to-peak noise voltage |
≤ 200 mV (0–20 MHz) |
|
Others |
No damage is caused if a storage battery is connected reversely. |
|
AC input protection |
AC input overvoltage protection threshold |
Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default). |
AC input overvoltage recovery threshold |
When the voltage is restored to 290 V AC, the output resumes. |
|
AC input undervoltage protection threshold |
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (85 V AC by default). |
|
AC input undervoltage recovery threshold |
When the voltage is restored to 90 V AC, the output resumes. |
|
DC output protection |
DC output overvoltage protection threshold |
58.5–60.5 V DC |
EMC |
CE |
CISPR 22 class A (AC terminal, DC terminal and Signal terminal) |
RE |
CISPR 22 Class A |
|
Harmonic |
IEC 61000-3-2 |
|
Fluctuation and blinking |
IEC 61000-3-3 |
|
ESD |
Standard: IEC61000-4-2 Contact discharge voltage: 6kV (Class B); air discharge voltage: 8 kV (Class B); |
|
EFT |
|
|
RS |
Standard: IEC61000-4-3 10 V/m |
|
CS |
Standard: IEC61000-4-3 |
|
SURGE |
Standard: IEC61000-4-5 The voltage at the AC power ports in differential mode is ±2 kV (criterion B). The voltage at the AC power ports in common mode is ±4 kV (criterion B). |
|
Others |
AC surge protection |
Level-B surge protection
|
Safety and regulatory design |
IEC60950-1, IEC 60950-22 |
|
MTBF |
100,000 hours |
|
Structure |
Dimensions (H x W x D) |
Cabinet (without base): 1400 mm x 650 mm x 700 mm (55.11 in. x 25.59 in. x 27.56 in.). Base: 100 mm x 650 mm x 700 mm (3.94 in. x 25.59 in. x 27.56 in.) |
Weight |
200 kg (without storage batteries and rectifiers) |
|
Space for customer |
More than 10U |
|
Protection level |
Equipment compartment is IP55 Battery compartment is IP23 |
|
Installation and carrying |
Mounted on concrete pad and carried by using a hoist |
|
Maintenance |
From the front, supporting module-level replacement. |
|
Cabling |
Bottom inlet and bottom outlet |
|
Heat dissipation mode |
Direct ventilation |
|
Heat dissipation capability |
More than 1500 W |