Schneider Easergy P3U20, 4L ringlug, 1U, 10DI/5DO, Uaux: 48-230V, DI: 24-230V, 2 x LC (REL52036)

Rp30.953.216

Deskripsi

Spesifikasi

Main
Range of product Easergy P3
Product or component type Protection relay
Relay application Universal
product reference P3U20-6AAA1ADAA
power supply 48…230 V AC/DC
measuring inputs : 1/5 A CT phase current 3
: 1/5 A CT residual current 1
: 100 V/110 V VT voltage 1
Number of sensors 0 temperature sensor(s)
0 arc sensor(s)
number of Digital Inputs (DI) 10
number of Digital Outputs (DO) 1 watchdog
5
number of analogue inputs 0
number of analogue outputs 0
communication ports USB port 1 front
LC 2 rear
communication protocols IEC 61850 ed. 1
IEC 61850 ed. 2
IEC 60870-5-101
DNP3 TCP
Modbus TCP
EtherNet/IP
Redundancy communication port protocol RSTP
PRP
Cybersecurity Port hardening
Password protection
protection functions Phase undercurrent 37
Negative sequence overcurrent 46
Broken conductor 46 I2/I1
Excessive starting time, locked rotor 48/51LR
Thermal overload protection 49
Phase overcurrent 50/51
Earth fault overcurrent 50N/51N
Breaker failure 50BF
Switch ON to fault (SOTF)
Capacitor bank unbalance 51C
Capacitor overvoltage 59C
Neutral voltage displacement 59N
Motor restart inhibition 66
Directional earth fault 67N
Transient earth fault 67NI
CT supervision 60
VT supervision 60
H2 detection 68H2
H5 detection 68H5
Recloser 79
Lockout relay 86
Cold load pick-up
Programmable stages 99
Programmable curve
Arc flash protection No
measurement functions Current 3-phase
Current zero sequence
Current positive sequence
Current negative sequence
Current ratio of negative and positive
Voltage phase to earth
Voltage phase to phase
Voltage zero sequence
Voltage positive sequence
Voltage negative sequence
Voltage ratio of negative and positive
Short circuit fault reactance
Fault location current
Earth fault reactance
Frequency
Active power
RMS active power
Reactive power
RMS reactive power
Apparent power
RMS apparent power
Active energy
Reactive energy
Cos φ
Tan φ
Power angle
Power factor
Voltage phasor diagram view
Current phasor diagram view
Current 2nd, 15th harmonics with THD
Voltage 2nd, 15th harmonics with THD
Voltage interruption
Condition monitoring CB wear
control functions Switchgear control and monitoring
Programmable switchgear interlocking
Local control on single-line diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with Easergy SmartApp
Web-server
Programmable logic
controllable switchgear devices 2 controlled + 4 displayed
number of setting groups 4
monitoring functions Trip circuit supervision 74
Circuit breaker monitoring
Relay self-monitoring
logs and records Event recording
Disturbance recording
Tripping context
Switchgear diagnosis type CT supervision
Trip circuit supervision ANSI code: TCS
Connections – terminals Screw removable (digital input/output)
Ring lugs removable (current transformer)
Pin removable (voltage transformer)
Complementary
Operating threshold 24…230 V AC/DC
web server Embedded HTTP server
Software name EcoStruxure Power Device
ESetup Easergy Pro
Display type And LCD 128 x 64 pixels with single line diagram
Number of key 2 customizable
Local signalling 4 LEDs
8 LEDs programmable
Standards IEC
Height 169.5 mm
Width 170 mm
Depth 205 mm
Net weight 2.5 kg maximum
Environment
Electromagnetic compatibility Emission tests conforming to IEC/EN 60255-26 ed. 3
Emission tests class A conforming to CISPR 11
Emission tests class A conforming to CISPR 22
EMC immunity conforming to IEC/EN 60255-26 ed. 3
EMC immunity conforming to EN/IEC 61000-4-18
EMC immunity level 4 conforming to EN/IEC 61000-4-2
EMC immunity level 3 conforming to EN/IEC 61000-4-3
EMC immunity level 4 conforming to EN/IEC 61000-4-4
EMC immunity level 3 conforming to EN/IEC 61000-4-5
EMC immunity level 3 conforming to EN/IEC 61000-4-6
EMC immunity conforming to EN/IEC 61000-4-8
EMC immunity level 5 conforming to EN/IEC 61000-4-9
EMC immunity conforming to EN/IEC 61000-4-29
EMC immunity conforming to EN/IEC 61000-4-11
EMC immunity conforming to EN/IEC 61000-4-17
Mechanical robustness Vibrations (level: class II) conforming to IEC 60255-21-1
Vibrations: Fc conforming to IEC 60068-2-6
Shocks (level: class II) conforming to IEC 60255-21-2
Shocks: Ea conforming to IEC 60068-2-27
Seismic tests method A (level: class II) conforming to IEC 60255-21-3
Bumps (level: class II) conforming to IEC 60255-21-2
Bumps: Ea conforming to IEC 60068-2-27
climatic withstand Exposure to dry heat Bb tests conforming to EN/IEC 60068-2-2
Exposure to cold Ad tests conforming to EN/IEC 60068-2-1
Exposure to damp heat in service Db tests conforming to EN/IEC 60068-2-30
Exposure to damp heat in service Cab tests conforming to EN/IEC 60068-2-78
Ambient air temperature for operation -40…65 °C
Ambient air temperature for storage -40…70 °C
IP degree of protection IP54 conforming to IEC 60529
Relative humidity 0…95 %, without condensation
maximum operating altitude 2000 m
Protective treatment Conformal coating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 16 cm
Package 1 Width 21.5 cm
Package 1 Length 27.5 cm
Package 1 Weight 3.5 kg
Datasheet-Easergy P3 Protection Relays_REL52036.pdf